Rating |
7.5kVA |
10kVA |
12kVA |
15kVA |
20kVA |
| Output power factor |
0.7 |
| Double conversion AC-AC efficiency 100% linear load cos phi? = 0.8ind |
93% |
94% |
94.5% |
| Heat dissipation with 100% load cos ? = 0.8ind |
380 |
500 |
550 |
700 |
800 |
| Audible noise with 100%/50% load |
50/47 dBA |
53/49 dBA |
| Ambient temperature for UPS |
0 - 40degC |
| Ambient temperature for batteries (recommended) |
20 - 25 degC |
| Input voltage - single phase |
220 - 240V |
N/A |
| Input voltage - three phase |
220 - 415V/ph |
N/A |
220 - 415V/ph |
| Input voltage window @ 3 x 400/230V |
For loads:
<100% (-23%, +15%)
<80% (-30%, +15%)
<60% (-40%, +15%)
|
| Input frequency window |
35 - 70 Hz |
| Input power factor |
Single-phase input: 0.98@100%load
Three-phase input: 0.95@100% load 0.98 optional
|
| Output rated voltage |
1 X 220V, 1 X 230V, 1 X 240V |
| Output power factor |
0.7 |
| Output waveform |
Sinewave |
| Output frequency |
50Hz or 60 Hz |
| Overload capability |
|
|
|
|
|
| Max autonomy @ full load - Cab A |
17 min |
10 min |
7 min |
4 min |
N/A |
- Cab B |
70 min |
55 min |
42 min |
28 min |
20 min |
- Cab C |
210 min |
170 min |
150 min |
105 min |
65 min |
| Dimensions WxDxH mm |
Cab A 340 x 800 x 820 |
Cab B 450 x 860 x 1250 |
Cab C 550 x 890 x 1650 |
| Footprint |
0.25m² |
0.37m² |
| Weight Cabinet A |
75kg |
N/A |
| Weight Cabinet B |
154kg |
| Weight Cabinet C |
204kg |