kVA |
10 |
15 |
20 |
30 |
40 |
60 |
80 |
100 |
120 |
160 |
200 |
250 |
No of parallel modules |
No limit |
Output power factor |
0.8 |
Internal battery mins @ full load |
37 |
20 |
13 |
6 |
9 |
External battery cabinet(s) |
External batteries |
Extended battery autonomies available to meet load requirements |
Input voltage |
380 to 415V -25% +15% |
Input frequency |
35 to 65 Hz |
45 to 65 Hz |
Input power factor |
0.98 regulated |
Input current THD |
<9% |
Output voltage |
380 to 415V |
Output frequency |
50 or 60 Hz |
Output voltage tolerance - static |
±1% |
- At load step (0-100-0 |
±4% |
-Distortion with nonlinear load |
±3% |
<4% |
Crest factor |
3:1 |
Overload capacity |
125% for 10 minutes, 150% for 1 minute |
Monitoring and control |
LCD panel/RS232/Volt-free contacts/EPO |
Standards |
EN 50091 Parts 1, 2 and 3 |
Protection |
IP20 |
Efficiency AC - AC |
Up to 97% on line |
Audible noise |
55 to 61 dBA |
61 to 73 dBA |
Mechanical Data |
|
Dimensions WxHxD mm |
550 x 1400 x 750 |
550 x 1800 x 750 |
580 x 1400 x 750 |
580 x 1800 x 750 |
700 x 1900 x 750 |
1200 x 1900 x 750 |
Weight Kg (UPS without batteries) |
180 |
185 |
185 |
190 |
260 |
190 |
220 |
330 |
350 |
620 |
640 |
660 |