You can 'right size' your system - right capacity, right redundancy and right future expansion provision - by selecting an MD or MF frame and populating it with DPA modules of 10 -50kVA rating each to efficiently meet your needs.
Module range |
MD |
MX |
UPS Module Type |
DPA10 |
DPA15 |
DPA20 |
DPA25 |
DPA30 |
DPA40 |
DPA50 |
Output rated power per module PF 0.8 |
KVA |
10 |
15 |
20 |
25 |
30 |
40 |
50* |
Output rated power per module PF 1.0 |
KW |
8 |
12 |
16 |
20 |
24 |
32 |
40 |
Efficiency AC-AC at PF=0.8 |
% |
Depending on module power and load, ranges from 92 to 95.4% |
Eco-mode efficiency at 100% load |
% |
98% |
Output rated voltage |
V |
3 x 380/220V or 3 x 400/230V or 3 x 415/240V |
Output frequency |
Hz |
50 or 60 |
Nominal input voltage |
V |
3 x 380/220V+N, 3 x 400/230V+N, 3 x 415/240V+N |
Input frequency |
Hz |
35 - 70 |
Input Power Factor |
|
PF=0.99@100% load |
Inrush current |
A |
Limited by Soft Start/Max.In |
Input Current Distortion THDi |
|
Sinewave THDi=<2%@ 100% load |
Overload capability on inverter |
% |
125% load for 10 minutes
150% load for 60 seconds |
Audible noise at 100%/50% load |
dBA |
55/49 |
57/49 |
57/49 |
57/49 |
59/51 |
65/55 |
65/55 |
Operating temperature |
°C |
0 to 40 |
Storage temperature |
°C |
-25 to +70 |
Relative Air- humidity |
|
Maximum 95% (non-condensing) |
Accessibility |
|
Totally front accessible for service and maintenance - no need for top, rear or side access |
*Static bypass mode 45kVA/40KW |