When an uninterruptible power supply (UPS) is operating at significantly under capacity, its energy efficiency can be negatively impacted. With PowerWAVE 9500DPA, featuring Xtra VFI, this problem is solved. Xtra VFI mode is a smart way to minimize losses and improve efficiency when running in double conversion mode.

How does it work?

With Xtra VFI mode enabled, the PowerWAVE 9500DPA automatically adjusts the number of active modules according to the load requirements. Modules that are not needed are switched to standby but remain in state of readiness, primed to kick in and transfer to active mode if the load increases. The efficiency improvements achieved by this mode of operation are especially significant when the load is less than 25 percent of full UPS system capacity. In addition, Xtra VFI has the added benefit of rotating modules between active and standby, therefore extending the service life of the UPS.

The figure below shows how the Xtra VFI operating mode can enhance efficiency when running at a low load level for a PowerWAVE 9500DPA modular UPS system, with 10 UPS modules (100 kW) and total available capacity of 1 MW.

ACTIVE :

The UPS module is operating at double conversion mode and supplying the load with the other active modules. Each module equally shares the load

PASSIVE :

The UPS module is on standby, with the inverter switched off, ready to transfer to active double conversion operation when the load increases

Key features:

  • Xtra VFI scales the UPS module active capacity according to the load to maximise efficiency
  • The system calculates the optimal % value for maximum efficiency, taking into account desired redundancy
  • The redundancy level for active capacity and the highest expected load step can be configured by the user to guarantee highest protection level
  • In case of mains failure or alarm, Xtra VFI gets deactivated automatically. In this situation all modules switch to ‘Active’ status
  • Module rotation between active and standby extends the service life and stabilises aging

For more information on the PowerWAVE 9500DPA and the Xtra VFI Feature, Contact us on 0800 731 3269, email us at sales@upspower.co.uk, or alternatively use the Contact form below:

GET A QUOTE

Are you interested? Call us on 01256 386700 or complete the form below, and let us supply you with a quote. Required Info*








We would like to keep in touch with you from time to time! If you would like to hear from us, please let us know what you are interested in:

To learn more about these options and what they mean, please view our Marketing Communications page.

Example:

  • Maximum load = 800 kW
  • Redundancy = N+2
  • 2 x 500 kW frames (10 x 100 kW)
  • Load power = 200 kW
  • No. of active modules = 4
  • UPS active capacity = 400 kW
  • UPS standby capacity = 600 kW